Fire Fighter-HRFR

Electrolytic copper thin strands are drawn in multiple directions to ensure consistency in resistance, dimensions, and flexibility. The drawn threads are compressed and precisely uni-laid. creating a completely round conductor as a result, allowing for a reduction in total diameter to save space in high density wiring.
PVC insulation that has been specially blended to be flame- and heat-resistant to 105 degrees is employed. The HR FR characteristic slows the spread of fire without endangering people’s safety.
The generic marking “KVVS WIRES AND CABLES FIRE FIGHTER-HRFR 105°C” is printed on the cables.
Red, yellow, green, blue, black, grey, and white. Additional colours can be requested.
90 meters, 180 meters, 270 meters, or 100 yards of packing.

DIMENSIONS, RATINGS, AND SIZE: VOLTAGE GRADE 1.1 KV SINGLE CORE UNSHEATHED CABLES AS IS 694 : 2010

Nominal Cross Sectional Area of Conductor
Nos/Nom. Dia of Conductor Strands
Thickness of Insulation
Approx Overall Diameter
Current Carrying Capacity $2 Wires, Single Phase.
Maximum Conductor Resistance @ 20 ⁰C
Unenclosed-Clipped
Directly to Surface or on Cable Tray
In Conduit/ Cable Trunking
mm2
Nos/mm#
mm
mm
Amps
Amps
Ohm / km
0.75
19/0.23
0.6
2.2
9
8
26
1
37/0.19
0.7
2.7
15
14
19.50
1.5
37/0.23
0.7
2.9
18
16
13.30
2.5
61/0.23
0.8
3.7
25
23
7.98
4
61/0.3
0.8
4.3
33
29
4.95
6
91/0.3
0.8
4.6
44
40
3.30

Note: